TOTAL LIFETIME FAULTS

635

+12% YoY

633 occurrences of 302(00)

ENERGY LOSS (5 YRS)

952.5

kWh

Calculated based on 1.5kWh deficit per unhandled fault flag.

FINANCIAL BLEED

R$904.875

Calculated based on ENEL RJ tariff (~R$ 0.98/kWh) minus 15% PV2 inefficiency.

AI DIAGNOSTIC ENGINE

Grid Instability Detected

Error 302(00) maps directly to external grid (Enel) dropouts, not internal PV damage.

Daily Power Generation (PAC)

Live Telemetry from Growatt OpenAPI.

LIVE TELEMETRY (API TOKEN)42.5 kWh Today

5-Year Fault Distribution Map (2022-2026)

Hydrated from Grott historical database. Spikes correlate heavily with summer storm seasons.

Root Cause Analysis: Error 302(00)

What is Error 302? The "No AC Connection" error is strictly an AC-side fault. It means the inverter has completely lost its connection to the utility grid (Enel).

COMMON CAUSES (NOT PANEL RELATED)

  • Utility grid blackout or severe instability from Enel.
  • AC breaker protecting the inverter tripped under surge.
  • Physical disruption in the AC cables connecting to the main switchboard.

Critical Note: This is NOT caused by broken diodes, burnt panels, or missing consumption meters. It is a direct cut of AC power to the inverter.

[ STRING HEALTH ANALYZER ]

FALHA FÍSICA DETECTADA: PV2 ISOLADO
MétricaPV1 (Operacional)PV2 (CRÍTICO)Diferença / Prejuízo
Voltagem380.5V46.1V-334.4V (Falha de Continuidade)
Corrente8.2A0.0A100% de Perda
StatusMPPT AtivoSTALLEDAbaixo do Startup (100V)

Workers AI Expert Analysis: A inclinação atual em Niterói para o inverno deve ser de ~37°. Se os seus painéis estão fixos em 22°, você está jogando 15% de energia no lixo agora. A leitura de 46.1V no PV2 não é sombra, é defeito físico (MC4 derretido ou cabo rompido). Ação: Inspeção física imediata da String 2.

grott-tcp-listener ~/.logs
[2023-12-31 05:22:09]XZJ1BK50KZERR_302(00)No AC Connection1.After shutdown,Check AC wiring. 2.If error message still exists,contact manufacturer.
[2023-12-30 05:02:08]XZJ1BK50KZERR_302(00)No AC Connection1.After shutdown,Check AC wiring. 2.If error message still exists,contact manufacturer.